For use in solar power applications
Rated at 90°C for exposed or concealed wiring in wet or dry locations
The rated capacity is for direct burial catheters.
electrical character :
-Maximum operating voltage: 600 VRMS (UL PV)
physical characteristics :
-Temperature range: -40 °C to 90 °C
-Command AWG: 12 2000 AWG
-Conductor material: Soft-annealed tin-plated stranded copper, compliant with ASTM B-33 and EN 60228 standards
-Separator: Paper tape
-Insulation material: Halogen-free cross-linked polyethylene, thermosetting, especially polyolefin, specially designed for maximum flexibility
-Jacket material: UV-resistant PVC black, low-smoke, non-halogenated, flame-retardant, oil-resistant, wear-resistant, chemical-resistant, and UV-crosslinked compound, meeting UL 44 and UL 854 standards
--minutes. Bending radius: 8 times the diameter.
|
size |
conductor diameter |
number of piles |
insulation thickness |
nominal outside diameter |
net weight |
Maximum conductor resistance at 20 °C |
|
AWG perhaps MCM |
MM |
N |
MM |
MM |
kg/km |
Ω/KM |
|
250 |
13.21 |
36 |
3.04 |
19.8 |
504 |
0.232 |
|
500 |
18.68 |
36 |
3.04 |
25.3 |
894 |
0.116 |
|
750 |
23.06 |
58 |
3.43 |
30.4 |
1312 |
0.0774 |