Loading...

300/500V XLPE insulated, LSZH sheathed power cable (single core)

Single-core 300/500V XLPE insulated, LSZH sheathed power cables are mainly used in power plants, public transportation passenger systems, airports, petrochemical plants, hotels, hospitals, high-rise buildings, and other wiring applications.

Standard

Standard conforms to IEC 60502-1


Fire protection standards

Flammability (Single Vertical Wire Test)

EN 60332-1-2; IEC 60332-1-2; BS EN 60332-1-2; VDE0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1(C2);CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*

Reduce fire spread (vertical installation of cable bundles test)

EN 60332-3-24 (cat. C); IEC 60332-3-24; BS EN 60332-3-24;VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2(C1);CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4

Halogen-free

IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1;CEI 20-37/2-1; BS 6425-1*

No emission of corrosive gases

IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2;CEI 20-37/2-2; BS 6425-2*

Minimum smoke emission

IEC 61034-1&2; EN 61034 -1&2; DIN VDE 0482-1034-1&2;CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*

Toxic and harmful gases

NES 02-713; NF C 20-454

Note: * indicates that the standard has been superseded.
Rated voltage

300/500V


Cable structure

Conductor

Plain Annealed Copper, Multi-strand Stranded Compliant with IEC (EN) 60228 Class 2

Insulation

Cross-linked polyethylene composite

Outer Sheath

Thermoplastic LSZH compound, BS 7655-6.1 standard (LTS3 model; thermosetting LSZH compound, BS 7655-2.6 standard SW2-SW4 is also available). UV resistance, hydrocarbon resistance, oil resistance, rodent resistance, and termite resistance can all be provided as options.

Related products